Star Delta Starter: Complete Wiring Guide with Timer Calculations & Troubleshooting

Star delta starters are one of the most effective and economical methods for starting three-phase induction motors, particularly for medium to large motors ranging from 5 HP to 200 HP. By temporarily connecting the motor windings in star configuration during startup and then switching to delta for normal operation, this proven motor control method reduces starting current by approximately 33%, protecting both the motor and the electrical supply system from excessive inrush currents and mechanical stress.

Whether you're installing a new star delta motor starter, troubleshooting an existing installation, or selecting components like star delta contactors and timers, understanding the principles, wiring, and settings is essential for reliable motor operation. This guide covers everything from basic theory to practical installation, helping you master this fundamental motor control technique.

Table of Contents

  1. Understanding Star Delta Starting Principles
  2. Star Delta Starter Components
  3. Star Delta Wiring Diagrams
  4. Timer Settings and Calculations
  5. Component Selection Guide
  6. Installation and Commissioning
  7. Troubleshooting Common Problems

Understanding Star Delta Starting Principles

What is Star Delta Starting?

Star delta starting is a reduced voltage starting method for three-phase induction motors. The motor starts with its windings connected in star (Y) configuration, which applies reduced voltage to each winding. Once the motor reaches approximately 80-90% of rated speed, the connection automatically switches to delta (Δ) configuration for normal full-power operation.

Why Use Star Delta Starting?

Key Benefits:

AdvantageStar DeltaDirect-On-Line (DOL)
Starting Current2-3 times FLA6-8 times FLA
Starting Torque33% of DOL100% of rated
Mechanical StressReduced significantlyHigh impact
Supply System ImpactMinimal voltage dipSevere voltage dip
CostModerateLow
ComplexityMediumSimple

Star vs Delta Connection Theory

Star Connection (Y) - Starting Phase:

  • Each winding receives line voltage divided by √3 (approximately 58%)
  • Voltage per winding: Vwinding=Vline3V_{winding} = \frac{V_{line}}{\sqrt{3}}
  • Current per winding equals line current: Iwinding=IlineI_{winding} = I_{line}
  • Starting current: Istar=IDOL3I_{star} = \frac{I_{DOL}}{3}
  • Starting torque: Tstar=TDOL3T_{star} = \frac{T_{DOL}}{3}

Delta Connection (Δ) - Running Phase:

  • Each winding receives full line voltage
  • Voltage per winding: Vwinding=VlineV_{winding} = V_{line}
  • Current per winding: Iwinding=Iline3I_{winding} = \frac{I_{line}}{\sqrt{3}}
  • Full rated torque and current

Practical Example: For a 30 HP motor at 415V:

  • DOL starting current: 180A (6 times FLA of 30A)
  • Star delta starting current: 60A (2 times FLA)
  • Current reduction: 67%

When to Use Star Delta Starters

Ideal Applications:

  • Centrifugal pumps with low starting torque requirements
  • Fans and blowers
  • Compressors with unloaded start
  • Conveyors starting empty
  • Machine tools with light initial load

Not Suitable For:

  • High starting torque loads (conveyors, crushers)
  • Motors with single voltage rating
  • Applications requiring frequent starts
  • Very small motors (below 5 HP) - cost not justified
  • Motors that must accelerate quickly under load

Star Delta Starter Components

Essential Components

A complete star delta starter system consists of several key components working together:

1. Main Contactor (KM3 - Delta Contactor)

  • Carries full motor current during normal operation
  • Must be rated for motor full load amperes (FLA)
  • Typically largest contactor in the system
  • Closes after star contactor opens

2. Star Contactor (KM1)

  • Connects motor windings in star configuration
  • Can be smaller than main contactor (58% rating)
  • Opens before delta contactor closes
  • Active only during starting sequence

3. Line Contactor (KM2)

  • Controls power supply to motor
  • Rated same as main contactor
  • Remains closed during entire operation
  • First to close, last to open

4. Star Delta Timer Relay

  • Controls transition timing from star to delta
  • Adjustable delay typically 5-30 seconds
  • Critical for proper motor acceleration
  • Available in electronic or mechanical versions

5. Overload Relay

  • Protects motor from overcurrent
  • Set to motor nameplate FLA
  • Thermal or electronic types available
  • Must trip all three phases

6. Control Circuit Components

  • Push buttons (START/STOP)
  • Indicator lights (power, running, fault)
  • Auxiliary contactors for interlocking
  • Fuses or MCBs for control circuit protection

Component Rating Selection

For a 30 HP motor at 415V (FLA = 42A):

ComponentRatingSelection Criteria
Main Contactor (Delta)50A (AC3)1.2 × FLA minimum
Star Contactor32A (AC3)0.58 × Main contactor
Line Contactor50A (AC3)Same as main contactor
Overload Relay30-42A adjustableSet to motor FLA
Star Delta Timer5-15 secondsBased on motor acceleration
Control Fuses2AFor 230V control circuit

Star Delta Wiring Diagrams

Power Circuit Wiring

The power circuit connects the three-phase supply to the motor through the contactors:

Standard Power Circuit Configuration:

Star-Delta starter wiring diagram showing power circuit with main and star contactors and low-voltage control circuit for contactor coils

Complete Star-Delta starter diagram showing both high-voltage power circuit and low-voltage control/command circuit. Three-phase supply (L1, L2, L3) feeds the line contactor (KM2) and main contactor (KM3) to motor terminals U1, V1, W1. Star contactor (KM1) connects the motor star point U2, V2, W2. The low-voltage control circuit includes start/stop pushbuttons and control coils for KM1, KM2, and KM3 to manage the star-delta switching and reduce starting current.

Motor Terminal Connections:

  • U1, V1, W1: Start of each phase winding (delta terminals)
  • U2, V2, W2: End of each phase winding (star point)

During Star Starting:

  • KM2 (Line) closes: Connects supply to U1, V1, W1
  • KM1 (Star) closes: Shorts U2, V2, W2 together (star point)
  • Motor runs in star configuration

After Timer Delay:

  • KM1 (Star) opens: Breaks star point connection
  • Brief pause (0.05-0.1 seconds)
  • KM3 (Delta) closes: Connects U2→V1, V2→W1, W2→U1
  • Motor runs in delta configuration

Control Circuit Wiring

The control circuit manages the starting sequence and provides interlocking:

Basic Control Logic:

  1. START button pressed: Energizes line contactor (KM2) and star contactor (KM1)
  2. Timer starts: Begins countdown when star contactor closes
  3. Timer expires: De-energizes star contactor, energizes delta contactor
  4. Interlocking: Prevents simultaneous star and delta connection
  5. STOP button: De-energizes all contactors

Critical Interlocking Requirements:

  • Star and delta contactors must never close simultaneously
  • Mechanical and electrical interlocking required
  • Time delay between star opening and delta closing (typically 50-100ms)

warning

⚠️ Safety Warning: Simultaneous closure of star and delta contactors creates a direct short circuit between phases, causing severe equipment damage and potential electrical arc flash. Always implement both mechanical and electrical interlocking.

Typical Wiring Schematic

Power Circuit:

Star-Delta starter wiring diagram showing line, main, and star contactors connected to motor terminals U1, V1, W1 and star point U2, V2, W2

Star-Delta starter diagram showing 3-phase supply (L1, L2, L3) feeding a line contactor (KM2), then a main contactor (KM3) to motor terminals U1, V1, W1. Star contactor (KM1) connects the motor star point terminals U2, V2, W2, reducing starting current for three-phase motors.

Timer Settings and Calculations

Determining Optimal Timer Setting

The star delta timer delay must allow the motor to reach sufficient speed (typically 80-90% of rated RPM) before switching to delta. Setting the timer too short causes high current spikes during transition, while setting it too long wastes energy and may overheat the motor in star connection.

Calculation Method

Step 1: Determine Motor Acceleration Time

The acceleration time depends on motor and load inertia:

tacc=J×N9.55×Tavgt_{acc} = \frac{J \times N}{9.55 \times T_{avg}}

Where:

  • JJ = Total moment of inertia (kg·m²)
  • NN = Rated speed (RPM)
  • TavgT_{avg} = Average accelerating torque (N·m)

Step 2: Calculate Star Connection Time

The timer should be set to approximately:

ttimer=0.8×tacct_{timer} = 0.8 \times t_{acc}

This allows the motor to reach 80-90% of rated speed in star before switching to delta.

Practical Timer Settings by Motor Size

Based on typical applications (pumps, fans):

Motor PowerTypical Timer SettingAcceleration Characteristics
5-10 HP5-7 secondsQuick acceleration, light load
10-20 HP7-10 secondsModerate acceleration
20-50 HP10-12 secondsStandard industrial loads
50-100 HP12-15 secondsHeavy loads, higher inertia
Above 100 HP15-20 secondsVery high inertia systems

Timer Adjustment Procedure

Initial Setting:

  1. Set timer to middle of recommended range
  2. Start motor and observe current during transition
  3. Monitor motor speed using tachometer if available

Adjustment Criteria:

Timer Too Short (increase setting):

  • High current spike during star-delta transition
  • Motor stutters or hesitates during switching
  • Overload relay trips during transition
  • Supply voltage dips significantly

Timer Too Long (decrease setting):

  • Motor reaches full speed before transition
  • Excessive heat in motor during star operation
  • Inefficient starting process
  • Unnecessary delay in reaching full power

Optimal Setting Indicators:

  • Smooth transition from star to delta
  • Current spike during transition less than 1.5 × FLA
  • Motor at 85-90% of rated speed before switching
  • No overload trips or voltage dips

Schneider Star Delta Timer Configuration

Popular Schneider Electric timer relays for star delta applications:

RE7 Series:

  • Adjustable delay: 0.1-30 seconds
  • DIN rail mounting
  • LED indication
  • Control voltage: 24-240V AC/DC

RE9 Series:

  • Multi-function timer
  • Digital display
  • Precise adjustment
  • Memory backup

Typical Settings:

  • Function: Star delta (Y-Δ)
  • Star time: 8-12 seconds (adjustable)
  • Interlock time: 50-100ms
  • Control voltage: Match panel supply

Component Selection Guide

Contactor Selection Criteria

AC3 vs AC4 Duty Ratings

Contactors are rated based on utilization categories:

AC3 Rating (Normal Starting):

  • For motors with standard starting (star delta, normal conditions)
  • Switching occurs at approximately 1 times motor FLA
  • Longer electrical life
  • Use for main and line contactors in star delta starter

AC4 Rating (Heavy Duty):

  • For frequent starting, plugging, inching
  • Switching at 5-6 times motor FLA
  • Shorter electrical life but handles severe duty
  • Generally not required for star delta starting

Contactor Sizing Example

For 45 HP Motor at 415V (FLA = 60A):

Main Contactor (Delta - KM3):

  • Required current: 60A continuous
  • Selected rating: 75A (AC3)
  • Example: Schneider LC1D80 or Siemens 3RT1044

Star Contactor (KM1):

  • Required current: 60A × 0.58 = 35A
  • Selected rating: 50A (AC3)
  • Example: Schneider LC1D50 or Siemens 3RT1036

Line Contactor (KM2):

  • Required current: 60A continuous
  • Selected rating: 75A (AC3)
  • Same as main contactor

Overload Relay Selection

Motor Protection Settings:

The overload relay must be set to protect the motor without nuisance tripping:

Setting Range:

  • Minimum: 0.95 × Motor FLA
  • Maximum: 1.05 × Motor FLA
  • Typical: Exactly at motor nameplate FLA

Class Selection:

  • Class 10: Standard starting (trips in 10 seconds at 6× setting)
  • Class 20: Heavy starting loads (trips in 20 seconds at 6× setting)
  • Class 30: Very heavy starting (trips in 30 seconds at 6× setting)

For star delta starters, Class 10 is typically adequate since starting current is already reduced.

Complete Component List

For 30 HP Motor at 415V (FLA = 42A):

ComponentSpecificationQuantityExample Model
Main Contactor50A, AC3, 415V, 3-pole1Schneider LC1D50
Star Contactor32A, AC3, 415V, 3-pole1Schneider LC1D32
Line Contactor50A, AC3, 415V, 3-pole1Schneider LC1D50
Overload Relay30-42A, Class 101Schneider LRD340
Timer Relay0-30s adjustable, Y-Δ1Schneider RE7PA11BU
Start ButtonGreen, NO contact1XB4BA31
Stop ButtonRed, NC contact1XB4BA42
Running IndicatorGreen LED, 415V1XB4BVB3
Fault IndicatorRed LED, 415V1XB4BVB4
MCB63A, C-curve, 3-pole1For motor protection
Control Fuses2A, for 230V circuit2Control circuit protection

Installation and Commissioning

Pre-Installation Checks

Before wiring and energizing the star delta starter:

Motor Verification:

  1. Check nameplate: Confirm dual voltage rating (e.g., 380V/660V)
  2. Verify connections: Motor terminals U1, V1, W1, U2, V2, W2 accessible
  3. Insulation test: Megger test shows minimum 2MΩ at 500V DC
  4. Mechanical check: Motor rotates freely, bearings in good condition

Component Verification:

  1. Contactor ratings: Match calculated requirements
  2. Overload relay: Set to motor FLA
  3. Timer range: Covers required delay period
  4. Control voltage: Matches available supply (230V or 110V)

Wiring Procedure

Step-by-Step Installation:

1. Mount Components:

  • Install contactors and relays on DIN rail
  • Maintain adequate spacing for heat dissipation
  • Allow access for maintenance

2. Wire Power Circuit:

  • Connect incoming supply to line contactor (KM2)
  • Wire line contactor output to main and star contactors
  • Connect main contactor to motor terminals U1, V1, W1
  • Connect star contactor to motor terminals U2, V2, W2
  • Install jumpers between contactors for delta connection

3. Wire Control Circuit:

  • Connect control voltage supply (typically 230V)
  • Wire STOP button (NC contact) in series
  • Wire START button (NO contact) for control initiation
  • Connect timer relay with proper interlock logic
  • Install contactor auxiliary contacts for self-holding

4. Install Protection:

  • Mount overload relay in series with motor
  • Connect overload NC contact to break control circuit
  • Install control circuit fuse or MCB
  • Add indicator lights for status

Initial Commissioning

Pre-Energization Tests:

1. Visual Inspection:

  • Verify all connections tight and secure
  • Check wire sizing appropriate for current
  • Confirm no loose strands or exposed conductors
  • Verify mechanical interlocking in place

2. Continuity Tests:

  • Check control circuit continuity with power OFF
  • Verify contactor coils not short-circuited
  • Test overload relay continuity
  • Confirm timer relay connections

3. Insulation Tests:

  • Megger test between phases: >2MΩ
  • Megger test phase to ground: >2MΩ
  • Test at 500V DC for 1 minute

Start-Up Procedure:

1. Initial Power-On:

  • Energize control circuit first
  • Check indicator lights function
  • Verify stop button breaks circuit
  • Test start button initiates sequence (with motor supply OFF)

2. First Motor Start:

  • Set timer to mid-range (10 seconds)
  • Press START button
  • Observe star contactor closes (motor starts in star)
  • Verify timer begins counting
  • Observe transition to delta after timer expires
  • Motor should continue running in delta
  • Press STOP button and verify motor stops

3. Current Measurement:

  • Use clamp meter on each phase
  • Record starting current in star: Should be 2-3 × FLA
  • Record current during transition
  • Record running current in delta: Should equal FLA
  • Verify balanced currents across all three phases

4. Timer Optimization:

  • Adjust timer based on motor acceleration
  • Repeat starts with different timer settings
  • Find setting with smoothest transition
  • Document final timer setting

Troubleshooting Common Problems

Problem 1: Motor Won't Start

Symptoms:

  • No response when START button pressed
  • Control circuit not energizing

Possible Causes & Solutions:

CauseDiagnosisSolution
Control fuse blownCheck continuity of control fusesReplace fuse, investigate overcurrent cause
STOP button stuckTest STOP button continuity (should be closed)Replace or repair STOP button
Overload relay trippedCheck overload relay status indicatorReset overload, check motor current draw
Control voltage missingMeasure voltage at control terminalsCheck control transformer or MCB
Contactor coil openMeasure coil resistanceReplace faulty contactor

Problem 2: High Current During Star-Delta Transition

Symptoms:

  • Large current spike when switching from star to delta
  • Lights dim during transition
  • Overload occasionally trips during switching

Possible Causes:

1. Timer Set Too Short:

  • Motor hasn't reached sufficient speed
  • Solution: Increase timer setting by 2-3 seconds
  • Verification: Monitor motor speed, should be 85-90% before transition

2. Heavy Load:

  • Motor loading too high for star delta starting
  • Solution: Consider soft starter or reduce initial load
  • Verification: Check if load can be started unloaded

3. Transition Delay Too Short:

  • Insufficient time between star opening and delta closing
  • Solution: Verify interlock timing (50-100ms recommended)
  • Verification: Measure with oscilloscope if possible

Problem 3: Motor Overheats in Star Connection

Symptoms:

  • Motor body hot to touch during starting
  • Thermal overload trips during start sequence

Possible Causes:

1. Timer Set Too Long:

  • Motor running in star beyond necessary time
  • Solution: Reduce timer setting
  • Target: Motor should reach 80-90% speed, then switch

2. Excessive Starting Time:

  • Motor cannot reach speed in star configuration
  • Solution: Verify motor design suitable for star delta
  • Alternative: Consider soft starter or DOL with larger supply

Problem 4: Contactors Chatter or Buzz

Symptoms:

  • Audible buzzing from contactors
  • Contactors vibrate excessively

Possible Causes:

CauseSolution
Low control voltageVerify control voltage at least 85% of rated value
Shading coil damagedReplace contactor or repair shading ring
Contactor cores dirtyClean contactor faces, remove dust and debris
Loose connectionsTighten all control circuit connections
Undervoltage during startingCheck supply voltage, consider larger supply cables

Problem 5: Motor Runs in Star But Won't Switch to Delta

Symptoms:

  • Motor starts and runs in star configuration
  • Timer expires but delta contactor doesn't close
  • Motor continues running in star (reduced power)

Possible Causes:

1. Delta Contactor Failure:

  • Diagnosis: Check delta contactor coil voltage when timer expires
  • Solution: Replace delta contactor if coil or contacts faulty

2. Interlock Issue:

  • Diagnosis: Verify star contactor fully opens before delta closes
  • Solution: Check auxiliary contacts, adjust interlock timing

3. Timer Relay Failure:

  • Diagnosis: Measure output contact closure
  • Solution: Replace timer relay

Problem 6: Frequent Overload Trips

Symptoms:

  • Overload relay trips regularly during normal operation
  • Motor appears to run normally before trip

Possible Causes & Solutions:

1. Overload Set Too Low:

  • Check: Verify overload setting matches motor FLA
  • Solution: Adjust overload relay to motor nameplate current

2. Motor Overloading:

  • Check: Measure actual motor current with clamp meter
  • Solution: Reduce mechanical load or upgrade motor size

3. Voltage Imbalance:

  • Check: Measure voltage on all three phases
  • Solution: Correct supply system voltage imbalance (should be <2%)

4. Single-Phasing:

  • Check: Verify three-phase supply at motor terminals
  • Solution: Check for blown fuse or open contactor contact

Advanced Considerations

Star Delta vs Other Starting Methods

Comparison with alternative reduced voltage starting methods:

MethodStarting CurrentStarting TorqueCostComplexityBest For
Star Delta2-3 × FLA (33% of DOL)33% of DOLModerateMediumLight to moderate loads, 5-200 HP
Soft Starter2-4 × FLA (adjustable)30-80% (adjustable)HighLowSmooth acceleration, precise control
Auto-Transformer1.7-4 × FLA50-80% of DOLHighHighHigh torque requirements
DOL6-8 × FLA100%LowSimpleSmall motors, strong supply
VFD1-1.5 × FLA150%+ at low speedVery highMediumVariable speed, energy savings

Schneider Electric Star Delta Solutions

Schneider Electric offers complete star delta starter solutions:

TeSys U Line:

  • Integrated motor starters
  • Built-in star delta logic
  • Compact design
  • Motor sizes: 0.09-75 kW

TeSys D Contactors:

  • Modular contactor system
  • AC3 duty rated
  • Mechanical and electrical life optimization
  • Wide range: 9A to 800A

TeSys LR Overload Relays:

  • Thermal overload protection
  • Class 10, 20, or 30
  • Trip indication
  • Manual or automatic reset

PLC Integration

Modern installations often use PLCs for motor control:

PLC Control Advantages:

  • Flexible timer adjustment without hardware changes
  • Data logging of starts, run hours, trip events
  • Remote monitoring and control
  • Integration with plant SCADA systems
  • Advanced diagnostics and predictive maintenance

Basic PLC Logic for Star Delta:

When START:
  - Activate Line Contactor (KM2)
  - Activate Star Contactor (KM1)
  - Start Timer

When Timer Expires:
  - Deactivate Star Contactor (KM1)
  - Wait Interlock Time (100ms)
  - Activate Delta Contactor (KM3)

When STOP:
  - Deactivate all contactors
  - Reset timer

Conclusion: Mastering Star Delta Motor Starting

Star delta starters remain one of the most cost-effective and reliable methods for starting medium to large three-phase induction motors. By reducing starting current to approximately one-third of direct-on-line starting while maintaining adequate starting torque for most applications, star delta starters protect electrical systems and extend motor life.

Key Takeaways:

  1. Current Reduction: Star delta starting reduces starting current from 6-8 times FLA to just 2-3 times FLA
  2. Proper Motor Selection: Only works with motors having dual voltage ratings (delta at line voltage)
  3. Timer Critical: Set timer to allow motor to reach 80-90% speed before switching (typically 5-15 seconds)
  4. Component Sizing: Main contactor at motor FLA, star contactor can be 58% of main rating
  5. Interlocking Essential: Never allow star and delta contactors to close simultaneously
  6. Application Limits: Best for centrifugal loads (pumps, fans) with low starting torque requirements

Whether you're installing a Schneider star delta starter, troubleshooting an existing system, or designing a new motor control panel, understanding these fundamental principles ensures reliable, safe operation. Always verify motor suitability, properly size components, set timer correctly, and implement robust interlocking to prevent failures.

For motors requiring higher starting torque or more precise control, consider alternatives like soft starters or VFDs, but for the majority of pump and fan applications in the 5-200 HP range, star delta starting provides an optimal balance of performance, reliability, and cost.


Helpful Calculators


Credits


Share it:

Related Posts

Difference Between Contactor and Relay: Complete Guide with Applications & Selection Criteria

Understanding the **difference between contactors and relays** is crucial for electrical engineers, technicians, and anyone working with industrial control systems. While both devices serve as electr....

Read the article

Motor Overload Protection: Complete Sizing Guide with Charts & Selection Criteria

Motor overload protection is the most critical component in preventing costly motor failures and ensuring safe, reliable operation of electrical equipment. Motor overload relays protect against susta....

Read the article

PLC Programming Basics: Complete Beginner's Guide (Step-by-Step with Examples)

If you've ever wondered how modern factories operate with such precision and efficiency, the answer lies in PLC programming. Programmable Logic Controllers (PLCs) are the invisible workhorses behind ....

Read the article